Home      3-Phase Power Meter

3-Phase Power Meter ยป Three/3- Phase-Power Meter
Model: PCE-P43
3-Phase-Power Meter for monitoring of 3-phase network parameters / programmable / analogue output / modbus interface / DIN rail mounting
The power analyzer PCE-P43 is designed to take measurements and transfer measurement data of 3-phase power networks. The power transducers can be connected to symmetrical and asymmetrical systems. With thepower transducer currents can be measured directly, or indirectly through the transducer. It is possible to set the current transformer ratios of the power transducer via software. The complete setup of the power transducer is via front-mounted USB port. The measured values are converted by the power measuring transducer into a standard signal and transmitted via Modbus.The installation of the power transducer is on a DIN rail. In addition to the analogue data transfer from the power transducer, the power measuring transducer can via the built-in relays and alarms alert the user when under or in excess of a load. The power transducer can be used everywhere, where durable 3-phase networks need to be monitored. Application of the power transducer is especially useful in the area of energy management.
 

Specifications

Technical Data of the 3-Phase-Power Meter PCE-P43
Measuring size Measuring Range Accuracy of Mb.
Alternating current
(L1, L2, L3)
1 A AC
5 A AC
± 0.2 %
AC voltage
(L1, L2, L3)
2,9 ... 276 V AC (L-N)
10 ... 480 V AC (L-L)
± 0.2 %
± 0.5 %
Frequency
(L1, L2, L3)
47 ... 63 Hz ±0.1 %
Active power
(L1, L2, L3, ∑)
-1.65 ... 1.65 kW ± 0.5 %
Reactive power
(L1, L2, L3, ∑) 
-1.65 ... 1.65 kvar ± 0.5 %
Apparent power
(L1, L2, L3, ∑)
1.4 VA ... 1.65 kVA ± 0.5 %
Tan (phi)
(L1, L2, L3, ∑)
-1.2 ... 1.2 ± 1 %
Power factor
(L1, L2, L3, ∑)
-1 ... 1 ± 0.5 %
Active energy
(created / submitted)
(∑)
0 ... 99,999,999.9 kWh ± 0.5 %
Reactive energy
(capacitive / inductive)
(∑)
0 ... 99,999,999.9 kvarh ± 0.5 %
THD 0 ... 100 % ± 5 %
Output (numberselectable / max. 4) -20 ... 20 mA
Relay output (numberselectable / max. 4) Turnkey 250 V / 0.5 A AC
Pulse output Open collector, passive, 
Meets EN62053-31
5000 ... 20000 Imp/kWh progammable
Interface RS485 Modbus RTU 8N1, 8N2, 8E1, 8O1
Programming interface USB Modbus RTU 8N2
Dimensions 45 x 100 x 120 mm
Weight 300 g
Degree of protection IP40
Power supply (optional) 85 ... 253 V AC / DC
20 ... 50 V AC / DC
Operating conditions -10 ... 55 °C
0 ... 95 % r.F.
Storage conditions -30 ... 70 °C
0 ... 95 % r.F.
Measurement category CAT III / 300 V

 

ABOUT US

  • Head Office
  •    3-Syed Mauj Darya Road Lahore
  •    +92-42-37312378/37356445
  •    info@newchemical.com.pk
  • Karachi Office
  •    Humera Center Office # B13,
  •             188/1-A, Block-2, PECHS Karachi.
  •    +92-21-34526689
NEWSLETTER

Subscribe our newsletter gor get notification about new updates, etc.



@2018 NEW CHEMICAL CENTER All RIGHTS RESERVED.